Sparely
DU

TRIM SET,CONTROL VALVE,MODEL YO607,SS316

Material 4100043447 · TRIM SET · Plant 1000

AReorderCriticalStockout
Material
4100043447
Category
TRIM SET
Base unit
SET
MRP type
Non Stock
Criticality
A (3 of 8 FuncLocs A/B)
Supplier
No PO history
Lead time
159 d · P80 236 d
Unit price
Rp 78.5M (est.)

Recommendation

  • 1.Forecast 3.1 SET/year: 3.1 unplanned (credibility blend: own history + installed-base prior).
  • 2.Lead time ~159 days; expected demand during lead time 1.3.
  • 3.A 98.9% service level gives the lowest holding + downtime-risk cost: reorder at 6, order up to 9.
  • 4.On hand 0 + on order 0 is at or below the reorder point: order 9 now.
  • 5.Installed on 8 FuncLoc(s), 3 of them criticality A/B.
Proposed purchase requisition
9 SET
Rp 706.4M · order by 01 Oct 2026
Expected arrival ≈ 159 days
Price estimatedLead time estimated
On hand / on order
0 / 0
no open PO
Today Min / Max
0 / 0
static parameters in BoM
Rec. Min (reorder point)
6
safety stock 5
Rec. Max
9
order qty 3
Service level
98.9%
stockout risk now 36%
Unit price
Rp 78.5M
Category + unit estimate
ML early warning: 10% probability this part is needed in the next 90 days (below the 30% warning threshold). Inputs: 1 issue days in the last 180 days, last issue 1 days ago, 1 failure notifications on its equipment in 90 days, 0 planned jobs in 90 days, 0 PRs in 180 days.

Consumption history and 12-month forecast

Units per month. Turnaround issues (0 units) excluded from the baseline.

Demand pattern Single issue · 1 issue days · method: Credibility blend: own history + installed-base prior.

Cost of each service level

Annual holding vs downtime-risk cost for this part

Not stocking at all would cost Rp 1.6B/yr in expected downtime and emergency buys. A stockout here stops production with probability 1.07% for ~75 days.

Installed on 8 functional locations

3 with criticality A/B · 8 units installed

FuncLocCrit.InstalledNotificationsFailures / yr
PX_TCV-293
TEMPERATURE CONTROL VALVE
A100.12
PX_FCV-1487
BY PASS LINE
B100.11
PX_TCV-1241A
CL-1475 TEMP CONTROL
B100.12
PX_PCV-165C
PRESSURE CONTROL VALVE
C130.94
PX_FCV-1717
BY PASS LINE
C100.11
PX_FCV-456A
BY PASS LINE
C100.11
PX_LCV-1317A
VD-105C LEVEL CONTROL
C100.12
PX_PCV-1135
PP-1811A PRESSURE CONTROL
C100.08

Lead time and procurement

Lead time 159 ± 83 days (Category estimate, 0 PO lines) · on-time –

No purchase history: price and lead time are estimated from parts of the same category.

Planned maintenance demand (next 12 months)

No part-consuming maintenance job uses this part in the next 12 months.

Recent notifications on its equipment

DatePriorityFuncLocDescription
30 Sept 2026MediumPX_PCV-165C[MSI-B-26-AJT-261] Permanent repair
12 May 2026MediumPX_PCV-165CInstall scaffolding at PCV-165C
11 Jun 2025LowPX_PCV-165CPCV-165C stuck

Recent goods issues

Posting dateQtyOrderOrder type
30 Sept 20263201000010300Corrective