TRANSMITTER,TEMP,TYPE CE324,CS
Material 4100059023 · TRANSMITTER · Plant 1000
AReorderNormalSlow-moving
- Material
- 4100059023
- Category
- TRANSMITTER
- Base unit
- EA
- MRP type
- Stock Item
- Criticality
- A (6 of 13 FuncLocs A/B)
- Supplier
- No PO history
- Lead time
- 74 d · P80 126 d
- Unit price
- Rp 34.1M (est.)
Recommendation
- 1.Forecast 4.5 EA/year: 4.5 unplanned (credibility blend: own history + installed-base prior).
- 2.Lead time ~74 days; expected demand during lead time 0.9.
- 3.A 99.8% service level gives the lowest holding + downtime-risk cost: reorder at 4, order up to 6.
- 4.On hand 1 + on order 0 is at or below the reorder point: order 5 now.
- 5.Installed on 13 FuncLoc(s), 6 of them criticality A/B.
Proposed purchase requisition
5 EA
Rp 170.7M · order by 01 Oct 2026
Expected arrival ≈ 74 days
Price estimatedLead time estimated
On hand / on order
1 / 0
no open PO
Today Min / Max
1 / 2
static parameters in BoM
Rec. Min (reorder point)
4
safety stock 4
Rec. Max
6
order qty 2
Service level
99.8%
stockout risk now 23%
Unit price
Rp 34.1M
Category + unit estimate
ML early warning: 17% probability this part is needed in the next 90 days (below the 30% warning threshold). Inputs: 0 issue days in the last 180 days, last issue 315 days ago, 4 failure notifications on its equipment in 90 days, 0 planned jobs in 90 days, 0 PRs in 180 days.
Consumption history and 12-month forecast
Units per month. Turnaround issues (0 units) excluded from the baseline.
Demand pattern Single issue · 1 issue days · method: Credibility blend: own history + installed-base prior.
Cost of each service level
Annual holding vs downtime-risk cost for this part
Not stocking at all would cost Rp 3.5B/yr in expected downtime and emergency buys. A stockout here stops production with probability 1.07% for ~37 days.
Installed on 13 functional locations
6 with criticality A/B · 14 units installed
| FuncLoc | Crit. | Installed | Notifications | Failures / yr |
|---|---|---|---|---|
| PX_KT-419A TURBINE FOR KC-419A | A | 1 | 6 | 2.81 |
| PX_TIT-302A-59A TEMPERATURE | A | 1 | 0 | 0.04 |
| PX_PIT-1008 CONDENSATE PRESSURE | B | 1 | 2 | 0.47 |
| PX_DPT-1355 DIFF. PRESSURE | B | 1 | 0 | 0.06 |
| PX_LIT-1560 KC-372D LEVEL | B | 1 | 0 | 0.03 |
| PX_PIT-1531 HE-1967C PRESSURE | B | 1 | 0 | 0.04 |
| PX_DPT-1063 DIFF. PRESSURE | C | 1 | 0 | 0.06 |
| PX_LIT-1746C-25B CL-1481 LEVEL | C | 1 | 0 | 0.03 |
| PX_LIT-475 PP-1665 LEVEL | C | 1 | 0 | 0.03 |
| PX_KT-447 TURBINE FOR KC-447 | S | 1 | 13 | 6.24 |
| PX_KT-202 TURBINE FOR KC-202 | S | 1 | 4 | 2.81 |
| PX_KT-624A TURBINE FOR KC-624A | S | 2 | 3 | 2.39 |
Lead time and procurement
Lead time 74 ± 45 days (Category estimate, 0 PO lines) · on-time –
No purchase history: price and lead time are estimated from parts of the same category.
Planned maintenance demand (next 12 months)
No part-consuming maintenance job uses this part in the next 12 months.
Recent notifications on its equipment
| Date | Priority | FuncLoc | Description |
|---|---|---|---|
| 18 Sept 2026 | Medium | PX_KT-202 | Repair insulation KT-202 |
| 01 Sept 2026 | Low | PX_KT-447 | Replace lamp as per PM finding |
| 15 Jul 2026 | Medium | PX_KT-624A | [MSI-B-26-RXR-331/M] Replace line |
| 08 Jul 2026 | Medium | PX_KT-447 | Replace lamp as per PM finding |
| 13 May 2026 | Low | PX_KT-447 | KT-447 trip test |
| 19 Apr 2026 | Low | PX_KT-447 | Follow up after steam upset KT-447 |
| 03 Apr 2026 | Medium | PX_KT-419A | KT-419A steam leak at gland |
| 30 Mar 2026 | Low | PX_KT-447 | Leak from packing |
| 28 Mar 2026 | Medium | PX_KT-447 | Follow up after steam upset KT-447 |
| 17 Mar 2026 | Medium | PX_KT-419A | Install cover plate for MCP cracking |
Recent goods issues
| Posting date | Qty | Order | Order type |
|---|---|---|---|
| 20 Nov 2025 | 1 | 201000004964 | Corrective |