SPRING,SAFETY VALVE,SIZE HA979,GRAPHITE
Material 4100066184 · SPRING · Plant 1000
ASafety-criticalReorderCriticalStockout
- Material
- 4100066184
- Category
- SPRING
- Base unit
- EA
- MRP type
- Non Stock
- Criticality
- A (4 of 10 FuncLocs A/B, 4 safety/shutdown valve)
- Supplier
- No PO history
- Lead time
- 137 d · P80 196 d
- Unit price
- Rp 8.8M (est.)
Recommendation
- 1.Safety-critical element: installed on 4 safety or shutdown valve location(s). Downtime risk is costed as class A and at least 1 spare is always kept; any reduction needs Management sign-off.
- 2.Forecast 6.3 EA/year: 6.3 unplanned (credibility blend: own history + installed-base prior).
- 3.Lead time ~137 days; expected demand during lead time 2.4.
- 4.A 99.9% service level gives the lowest holding + downtime-risk cost: reorder at 9, order up to 13.
- 5.On hand 0 + on order 0 is at or below the reorder point: order 13 now.
- 6.Installed on 10 FuncLoc(s), 4 of them criticality A/B.
Proposed purchase requisition
13 EA
Rp 114.6M · order by 01 Oct 2026
Expected arrival ≈ 137 days
Safety-critical (SCE)Convert to Stock ItemPrice estimatedLead time estimated
On hand / on order
0 / 0
no open PO
Today Min / Max
0 / 0
static parameters in BoM
Rec. Min (reorder point)
9
safety stock 7
Rec. Max
13
order qty 4
Service level
99.9%
stockout risk now 79%
Unit price
Rp 8.8M
Category + unit estimate
ML early warning: 11% probability this part is needed in the next 90 days (below the 30% warning threshold). Inputs: 0 issue days in the last 180 days, last issue 355 days ago, 4 failure notifications on its equipment in 90 days, 0 planned jobs in 90 days, 0 PRs in 180 days.
Consumption history and 12-month forecast
Units per month. Turnaround issues (0 units) excluded from the baseline.
Demand pattern Intermittent · 2 issue days · method: Credibility blend: own history + installed-base prior.
Cost of each service level
Annual holding vs downtime-risk cost for this part
Not stocking at all would cost Rp 6.9B/yr in expected downtime and emergency buys. A stockout here stops production with probability 1.07% for ~77 days.
Installed on 10 functional locations
4 with criticality A/B · 10 units installed
| FuncLoc | Crit. | Installed | Notifications | Failures / yr |
|---|---|---|---|---|
| PX_KT-856A TURBINE FOR KC-856A | A | 1 | 7 | 2.81 |
| PX_KT-397A TURBINE FOR KC-397A | A | 1 | 5 | 2.81 |
| PX_PRV-192 SAFETY VALVE VD-884 | A | 1 | 2 | 0.90 |
| PX_KT-308B TURBINE FOR KC-308B | A | 1 | 0 | 1.10 |
| PX_KT-447 TURBINE FOR KC-447 | S | 1 | 13 | 6.24 |
| PX_KT-624A TURBINE FOR KC-624A | S | 1 | 3 | 2.39 |
| PX_PRV-1734D SAFETY VALVE KC-551D | S | 1 | 2 | 0.47 |
| PX_KT-875 TURBINE FOR KC-875 | S | 1 | 0 | 1.10 |
| PX_PRV-1185 SAFETY VALVE HE-171A | S | 1 | 0 | 0.04 |
| PX_PRV-1401 SAFETY VALVE PP-1250 | S | 1 | 0 | 0.04 |
Lead time and procurement
Lead time 137 ± 65 days (Category estimate, 0 PO lines) · on-time –
No purchase history: price and lead time are estimated from parts of the same category.
Planned maintenance demand (next 12 months)
No part-consuming maintenance job uses this part in the next 12 months.
Recent notifications on its equipment
| Date | Priority | FuncLoc | Description |
|---|---|---|---|
| 01 Sept 2026 | Low | PX_KT-447 | Replace lamp as per PM finding |
| 20 Jul 2026 | Low | PX_KT-856A | Follow up after steam upset KT-856A |
| 15 Jul 2026 | Medium | PX_KT-624A | [MSI-B-26-RXR-331/M] Replace line |
| 08 Jul 2026 | Medium | PX_KT-447 | Replace lamp as per PM finding |
| 26 May 2026 | Low | PX_KT-397A | Follow up after steam upset KT-397A |
| 16 May 2026 | Medium | PX_KT-397A | Replace lamp as per PM finding |
| 14 May 2026 | Low | PX_KT-397A | KT-397A trip test |
| 13 May 2026 | Low | PX_KT-447 | KT-447 trip test |
| 19 Apr 2026 | Low | PX_KT-447 | Follow up after steam upset KT-447 |
| 02 Apr 2026 | Medium | PX_KT-397A | Follow up after steam upset KT-397A |
Recent goods issues
| Posting date | Qty | Order | Order type |
|---|---|---|---|
| 11 Oct 2025 | 1 | 205000020548 | Other maintenance |
| 20 Aug 2025 | 2 | 201000004910 | Corrective |